TRANSFORMERS
SECTION NINE
All transformers
and coils are tested the same way. This includes chokes, coils, inductors, yokes, power
transformers, EHT transformers (flyback transformers), switch mode transformers, isolation
transformers, IF transformers, baluns, and any device that has turns of wire around a
former. All these devices can go faulty.
The coating on
the wire is called insulation or "enamel" and this can crack or
become overheated or
damaged due to vibration or movement. When two turns touch each other, a very interesting thing
happens.
The winding becomes two separate windings
We will take the
case of a single winding such as a coil. This is shown in the first diagram above and the winding is
wound across a former and back again, making two layers. The bottom and top layers touch at the point
shown in the diagram and the current that originally passed though A, B, C, D now passes though A &
D.
Winding B C
becomes a separate winding as shown in the second diagram.
In other words
the coil becomes a TRANSFORMER with a SHORT CIRCUIT on the secondary winding as shown in the
third diagram.
When the output
wires of a transformer are shorted together, it delivers a very high current because you have created a
SHORT-CIRCUIT. This short-circuit causes the
transformer to get very hot.
That’s exactly
what happens when any coil or transformer gets a “shorted turn.”
The shorted
turns can be a single turn or many turns.
It is not possible
to measure a fault like this with a multimeter as you don’t know the exact resistance of a working coil
or winding and the resistance of a faulty winding may be only 0.001 ohms less.
However when a
transformer or coil is measured with an inductance meter, an oscillating voltage (or spike) is
delivered into the core as magnetic flux, then the magnetic flux collapses and passes
the energy into the winding to produce a waveform. The inductance meter reads this and produces a value of
inductance in
Henry (milliHenry
or microHenry.)
This is done
with the transformer removed from the circuit and this can be a very difficult thing to do, as most
transformers have a number of connections.
If the coil or
transformer has a shorted turn, the energy from the magnetic flux will pass into the turns that are
shorted and produce a current. Almost no voltage will be detected from winding.
The reading from
the inductance meter will be low or very low and you have to work out if it is correct.
However there is
one major problem with measuring a faulty transformer or coil.
It may only
become faulty when power is applied.
The voltage
between the turns may be sparking or jumping a gap and creating a problem. A tester is not going to
find this fault.
Secondly, an
inductance meter may produce a reading but you do not know if the reading is correct. An improved
tester is a RING TESTER.
The circuit for
a ring tester can be found here:
It sends a pulse
to the coil and counts the number of returning pulses or
"rings." A faulty coil (or winding) may return
one pulse but nearly all the energy will be passed to the shorted turns and you will be
able to see this on the scale. You will only get one or two return pulses, whereas a good
winding will return more pulses.
One way to
detect a faulty power transformer is to connect it to the supply and feel the temperature-rise (when nothing is
connected to the secondary).
It should NOT
get hot.
Detecting
shorted turns i s not easy to diagnose as you really need another identical component to compare the results.
Most
transformers get very hot when a shorted turn has developed. It may deliver a voltage but the heat generated and
a smell from the transformer will indicate a fault
ISOLATION
TRANSFORMER
An isolation
transformer is a piece of Test Equipment that provides "Mains
Voltage" but the voltage is "floating." You will still get a shock if you
touch the two output leads, but it has a special use when testing unknown equipment.
Many electrical
appliances are fully insulated and only have two leads connected to the mains.
When you take
these appliances apart, you do not know which end of say a heating element is connected to the
"live" (active) side of the mains and which end connects to the neutral.
I am not
suggesting you carry out the following tests, but they are described to show how an isolation transformer works.
If you touch a
soldering iron on the "live" (active) end of the heating element it
will cause a short-circuit.
However when the
appliance is connected to the main via an
isolation transformer, you can touch an earthed soldering
iron on either end of the heater as both leads from the isolation transformer are
"floating."
Note: As soon as
you earth one lead of the output an isolation transformer, the other lead becomes "active." You can make your own Isolation Transformer by connecting two identical transformers
"back-to-back."
The following
diagram shows how this is done:
You can use any
transformers providing the primary and secondary voltages are the same. The current capability of the
secondary winding does not matter. However if you want a supply that has almost the same voltage as your
"Mains," you need two transformers with the same voltages.
This handy
isolation transformer will provide you with "Mains Voltage" but with
a limited current.
In other words
it will have a limited capability to supply "wattage." If you are
using two 15VA
transformers, you will only be able to test an appliance rated at 15 watts.
This has some
advantages and some disadvantages.
If you are
working on a project, and a short-circuit occurs, the damage will be limited to 15 watts.
If you are using
two transformers with different VA ratings, the lower rating will be the capability of the combination.
If the
secondaries are not equal, you will get a higher or lower "Mains
Voltage."
If you get two
old TV's or Monitors with a rating on the compliance plate of 45 watts, or 90 watts, you can assume the
transformers are capable of delivering this wattage and making an isolation transformer
will enable you to test similar items with the safety of being isolated from the mains.
Colin Mitchell
designs a lot of "LED lighting lamps" that are connected directly to
the mains. He always works
with an isolating transformer, just to be safe.
Working on exposed "mains" devices is extremely nerve-wracking and you have
to very careful.
DETERMINING THE SPECS OF A TRANSFORMER
Suppose you have
a "mains transformer" with unknown output voltages and unknown current capability. You must be sure it is a mains transformer
designed for operation on 50Hz or 60Hz.
Switch-Mode
transformers operate at frequencies 40kHz and higher and are not covered in this discussion.
To be on the
safe-side, connect the unknown transformer to the output of your isolating transformer.
Since the
transformer will take almost no current when not loaded, the output voltages it produces will be fairly
accurate. Measure the input AC voltage and output AC voltage.
If the
transformer has loaded your isolating transformer it will be faulty.
Mains transformers
are approx 15 VA for 500gm, 30VA for 1kgm
50VA for 2kgm and 100VA for 2.5kgm.
VA stands for
Volts-Amps and is similar to saying watts. Watts is used for DC circuits, while VA refers to AC circuits.
Once you have
the weight of the transformer and the output voltage, you can work out the current capability of the
secondary.
For transformers
up to 30vA, the output voltage on no-load is 30% higher than the final "loaded voltage."
This is due to
the poor regulation of these small devices.
If the
transformer is 15VA and the output voltage will be 15v AC, the current will be
1 amp AC.
You can check
the "quality" of the transformer, (the regulation) by fully loading
the output and measuring
the final voltage. If the transformer has a number of
secondaries, the
VA rating must be divided between all the windings.
OPTO
ISOLATORS and OPTO COUPLERS
Opto Isolators
and Opto Couplers are the same thing. A common opto-coupler is 4N35. It is used to allow two circuits to
exchange signals yet remain electrically isolated. The signal is applied to the LED, which
shines on a silicon NPN phot o-transistor in the IC.
The light is
proportional to the signal, so the signal is transferred to the photo transistor to turn it on a proportional amount. Opto-couplers can hav e
Light Activated
SCR's,
photodiodes, TRIAC's and other semiconductor device s as an output. The 4N35 opto-coupler schematic is shown
below:
An opto-Coupler using a TRIAC
TESTING
AN OPTO COUPLER
Most multimeters
cannot test the LED on the input of an opto-coupler because the ohms range does not have a voltage
high enough to activate the LED with at least
2mA.
You need to
set-up the test-circuit shown above with a 1k resistor on the input and 1k5 on the output. When the 1k is
connected to 12v, the output LED will illuminate.
The opto-coupler
should be removed from circuit to perform this test.




Post a Comment